2 Service Information
2.1.
Operation range
2.1.1.
Power Supply
The applicable voltage range for each unit is given in the following table. The working voltage among the three phases must be
balanced within a 3% deviation from each voltage at the compressor terminals. The starting voltage must be higher than 85% of the
rated voltage.
2.1.2.
Indoor and Outdoor Temperature
• Model 50Hz CU-YL24HBE5, CU-YL28HBE5, CU-YL34HBE5, CU-YL43HBE5
Notice*:
This unit is still able to operate as a cooler with outdoor temperature as low as -5
°C in a non-living room,  such as a computer room,
with a room temperature of 21
°C or above, and room humidity up to 45%.
MODEL
Unit Main Power
Applicable Voltage
CU-
Phase, Volts
Hz
Max
Min
YL24HBE5                                     
YL28HBE5                                            
YL34HBE5                                               
YL43HBE5
1~240
50
264
216
1~230
50
253
207
1~220
50
242
198
Operating
Hz
Indoor Temp. (D.B./W.B.) (
°C)
Outdoor Temp. (D.B./W.B.) (
°C)
Max
Min
Max
Min
Cooling
50
32/23
21/15
43/-
-5*/-
Heating
50
27/-
16/-
24/18
-15/-
Page of 118