17.4.11  H30 (Compressor Discharge Temperature Sensor Abnormality) 
Malfunction Decision Conditions 
  During startup and operation of cooling and heating, the temperatures detected by the outdoor discharge pipe 
temperature sensor are used to determine sensor errors. 
 
Malfunction Caused 
 Faulty 
connector 
connection. 
 Faulty 
sensor. 
 Faulty 
PCB. 
 
Troubleshooting 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
When abnormality indication starts again.
For safety reason and to prevent
component breakdown, always switch
off the power before remove and
connect the component.
Is the measured resistance of the outdoor discharge pipe
temperature sensor matches the value specified in its
characteristic chart?
Is the connector connection normal?
YES
YES
Check the outdoor discharge pipe temperature sensor:
Plug out connector from the outdoor unit PCB.
Measure the resistance of the outdoor discharge pipe
temperature sensor.
Check the connector connection:
Turn off the power.
Check the connector connection.
Connector poor contact.
Correct the connection.
Defect in outdoor unit PCB.
Replace the outdoor unit PCB.
Defect in outdoor discharge pipe
temperature sensor.
Replace the outdoor discharge pipe
temperature sensor.