17.2. Sensible Capacity Chart
CS-E24MKDS  CU-E24MKD
CS-E28MKDS  CU-E28MKD
Outdoor Temp. (
“C)      
Indoor wet 
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0
“C
6.75
5.11
1.94
6.30
4.90
2.09
5.86
4.71
2.23
5.33
4.48
2.41
19.0
“C
6.80
2.12
19.5
“C
7.41
5.35
1.98
6.92
5.14
2.13
6.44
4.95
2.28
5.85
4.71
2.45
22.0
“C
8.07
5.55
2.01
7.54
5.34
2.17
7.02
5.15
2.32
6.38
4.91
2.50
Outdoor Temp. (
“C)      
Indoor wet 
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0
“C
7.59
5.75
2.33
7.09
5.52
2.50
6.59
5.30
2.68
6.00
5.04
2.89
19.0
“C
7.65
2.54
19.5
“C
8.33
6.02
2.37
7.79
5.79
2.55
7.24
5.57
2.73
6.59
5.30
2.94
22.0
“C
9.08
6.25
2.41
8.48
6.01
2.60
7.89
5.79
2.78
7.18
5.53
2.99
TC - Total Cooling Capacity (kW)
Indoor 27
“C/19“C
SHC - Sensible Heat Capacity (kW)
Outdoor 35
“C/24“C
IP - Input Power (kW)
Page of 113