CS-E24GKES, CU-E24GKE, CS-E28GKE, CU-E28GKE - Panasonic Air Conditioner Service Manual (repair manual). Page 71

Read Panasonic CS-E24GKES / CU-E24GKE / CS-E28GKE / CU-E28GKE Service Manual online

71
17.2. Sensible Capacity Chart
O CS-E24GKES  CU-E24GKE
O CS-E28GKE  CU-E28GKE
Outdoor Temp. (
°C)      
Indoor wet 
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0
°C
6.75
5.11
1.94
6.30
4.90
2.09
5.86
4.71
2.23
5.33
4.48
2.41
19.0
°C
6.80
2.12
19.5
°C
7.41
5.35
1.98
6.92
5.14
2.13
6.44
4.95
2.28
5.85
4.71
2.45
22.0
°C
8.07
5.55
2.01
7.54
5.34
2.17
7.02
5.15
2.32
6.38
4.91
2.50
Outdoor Temp. (
°C)      
Indoor wet 
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0
°C
7.59
5.75
2.33
7.09
5.52
2.50
6.59
5.30
2.68
6.00
5.04
2.89
19.0
°C
7.65
2.54
19.5
°C
8.33
6.02
2.37
7.79
5.79
2.55
7.24
5.57
2.73
6.59
5.30
2.94
22.0
°C
9.08
6.25
2.41
8.48
6.01
2.60
7.89
5.79
2.78
7.18
5.53
2.99
TC - Total Cooling Capacity (kW)
Indoor 27
°C/19°C
SHC - Sensible Heat Capacity (kW)
Outdoor 35
°C/24°C
IP - Input Power (kW)
Page of 78