17.2. Sensible Capacity Chart
Outdoor Temp. (
°C)
Indoor wet 
bulb temp.
30
35
40
46
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
TC
SHC
IP
17.0
°C
5.85
4.44
1.88
5.47
4.26
2.02
5.09
4.09
2.16
4.63
3.89
2.33
19.0
°C
5.90
2.05
19.5
°C
6.43
4.65
1.91
6.01
4.46
2.06
5.59
4.30
2.20
5.08
4.09
2.37
22.0
°C
7.00
4.82
1.95
6.54
4.63
2.10
6.09
4.47
2.24
5.53
4.26
2.42
TC - Total Cooling Capacity (kW)
Indoor 27
°C/19°C
SHC - Sensible Heat Capacity (kW)
Outdoor 35
°C/24°C
IP - Input Power (kW)
Page of 87