Read Panasonic CS-BE20TKD / CU-BE20TKD Service Manual online
85
17. Technical
Data
Technical data provided are based on the air conditioner running under free frequency.
17.1 Cool Mode Performance Data
Unit setting: Standard piping length, Hi Fan, Cool mode at 16°C
Voltage: 220-230V
Voltage: 220-230V
Indoor (°C)
Outdoor DB (°C)
DB WB
5 16 25 35
TC
SHC IP TC
SHC IP TC
SHC IP TC
SHC IP
27
19.0 2126 1944 448 2393 2099 306 2231 2052 406 2050 1992 525
22.0 2461 1603 357 2636 1705 293 2445 1611 401 2180 1510 527
22.0 2461 1603 357 2636 1705 293 2445 1611 401 2180 1510 527
23
15.7 1945 1925 420 2156 2135 316 2000 1966 410 1769 1752 525
18.4 2091 1535 439 2292 1626 308 2182 1604 407 1961 1505 526
18.4 2091 1535 439 2292 1626 308 2182 1604 407 1961 1505 526
20
13.3 1786 1768 430 2029 2008 323 1842 1824 412 1643 1627 524
15.8 1901 1491 452 2133 1616 316 1987 1555 409 1783 1461 525
15.8 1901 1491 452 2133 1616 316 1987 1555 409 1783 1461 525
(Dry bulb value based on 46% humidity)
TC - Total Cooling Capacity (W)
SHC - Sensible Heat Capacity (W)
IP - Input Power (W)
17.2 Heat Mode Performance Data
Unit setting: Standard piping length, Hi Fan, Heat mode at 30°C
Voltage: 220-230V
Voltage: 220-230V
Indoor (°C)
Outdoor WB (°C)
DB
-15 -7 2 7 12
TC IP TC IP TC IP TC IP TC IP
24 1518 743 1729 745 2254 781 2484 691 2644 688
20 1520 703 1900 740 2320 800 2800 690 2751 687
16 1432 665 1960 708 2335 761 2840 689 2916 686
20 1520 703 1900 740 2320 800 2800 690 2751 687
16 1432 665 1960 708 2335 761 2840 689 2916 686
TC - Total Cooling Capacity (W)
IP - Input Power (W)