Read Panasonic CS-A75KE / CS-A95KE / CS-A125KE / CU-A75KE / CU-A95KE / CU-A125KE Service Manual online
Compressor Protection Control
Automatic Fan Speed Mode
•
After the compressor starts for 50 seconds but the outdoor fan motor is still OFF, the compressor will stop and restart
automatically. (Time Delay Safety Control is valid).
automatically. (Time Delay Safety Control is valid).
•
If the above phenomenon is repeated for 3 times, the compressor will stops.
•
The above phenomenon is reset when there is a change to heating mode or stopped by Remote Control Switch.
When Automatic Fan Speed is selected at Remote Control during cooling operation.
•
Fan speed rotates in the range of Hi to Me.
•
Deodorizing Control.
18
S-A75KE CU-A75KE / CS-A95KE CU-A95KE / CS-A125KE CU-A125KE