Read Panasonic CS-A28JKD / CU-A28JKD Service Manual online
13
8 Wiring Connection Diagram
Resistance of Outdoor Fan Motor Windings
Note: Resistance at 20
qC of ambient temperature.
Resistance of Compressor Windings
Note: Resistance at 20
qC of ambient temperature.
MODEL
CU-A28JKD
CONNECTION
CWA951294J
BLUE - YELLOW
102
:
YELLOW - ORANGE
81
:
YELLOW - RED
108
:
MODEL
CU-A28JKD
CONNECTION
2JD514E3AA03
C - R
1.022
:
C - S
2.142
: