CS-A18CKE, CU-A18CKE, CS-A24CKE, CU-A24CKE - Panasonic Air Conditioner Service Manual (repair manual). Page 16

Read Panasonic CS-A18CKE / CU-A18CKE / CS-A24CKE / CU-A24CKE Service Manual online

Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Anti-Freezing Control
     • 
• 
• 
• If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
     • 
• 
• 
• Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
8.2. Cooling Mode Operation
     • 
• 
• 
• When the compressor is stopped by Remote Control, it restarts after 3 minutes when the Remote Control is turned ON.
     • 
• 
• 
• When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
     • 
• 
• 
• The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
     • 
• 
• 
• If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
! T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
     • 
• 
• 
• Purpose is to prevent dew formation on indoor unit air discharge area.
     • 
• 
• 
• When room temperature is constant (±1°C) the following conditions occur for 30 minutes continuously, anti-dew formation will
activate:
     − 
− 
− 
− Indoor intake air temperature is more than 24°C and less than 30°C.
     − 
− 
− 
− Remote Control setting temperature is less than 25°C.
     − 
− 
− 
− Compressor is on.
     − 
− 
− 
− Cooling operation mode.
     − 
− 
− 
− Indoor Fan motor operate at Low fan speed or QLo.
     • 
• 
• 
• This control is cancelled immediately when above condition is changed.
     • 
• 
• 
• Anti-Dew formation is control by:
 1. Lo fan speed
Lo fan is changed to Lo+ fan
16
CS-A18CKE CU-A18CKE / CS-A24CKE CU-A24CKE